ABB PowerValue 11T G2 2000VA Single Phase UPS
$1,364.90
ABB’s PowerValue 11 RT G2 is a double-conversion online UPS that guarantees clean, reliable power for your critical single-phase applications. As well as maintaining power to your servers, point-of-sale terminals, workstation clusters, routers, switches, hubs and sensitive electronic equipment, the PowerValue 11 RT G2 also conditions incoming power to eliminate spikes, swells, sags, noise and harmonics.
The PowerValue 11 RT G2 can be used as a standalone UPS device or installed into a standard 19" rack configuration, with connectivity options available for each. All units can be fitted with up to six battery modules to extend runtime.
New Generation of ABB UPS to replace the previous GE VH2000 systems.
Model: 4NWP100201R0011
HighLights:
• Reliable double conversion topology protects
load from all input disturbances
• Batteries can be added or replaced easily
• Reduced recovery time from discharge
• Unity or close to unity power factor (kW = kVA)
• Scalable runtime
• High operating efficiency, regardless of loading
• Reduced installation and upgrading costs
• Compact design
load from all input disturbances
• Batteries can be added or replaced easily
• Reduced recovery time from discharge
• Unity or close to unity power factor (kW = kVA)
• Scalable runtime
• High operating efficiency, regardless of loading
• Reduced installation and upgrading costs
• Compact design
• Configurable in tower or rack-mount format
• Rotatable display
• UPS can be connected with up to six external
battery modules (EBMs) for extended runtime
• Full set of accessories and connectivity options
• Easy set-up and maintenance (plug-and-play)
• User-friendly display
• Hot-swap user-replaceable internal batteries
• Rotatable display
• UPS can be connected with up to six external
battery modules (EBMs) for extended runtime
• Full set of accessories and connectivity options
• Easy set-up and maintenance (plug-and-play)
• User-friendly display
• Hot-swap user-replaceable internal batteries
SPECIFICATIONS
MODEL NUMBER |
4NWP100201R0011
|
|||||
Power rating | 2000VA (1930W) | |||||
Voltage nominal | 100 / 110 / 115 / 120 / 125 VAC | |||||
Voltage range | 55-150VAC (de-rating to 60% @60V) | |||||
Frequency | 45-55 Hz for 50 Hz systems; 54-66 Hz for 60 Hz systems | |||||
Voltage | 100 / 110 / 115 / 120 / 125 VAC | |||||
Waveform | Pure sine wave | |||||
Overload capacity (linear load) on inverter |
1.5 s: 140% load; 30 s: 130% load; 300 s: 110% load (line mode)1.5 s: 140% load; 10 s: 130% load; 120 s: 110% load (battery Mode) | |||||
Battery type | VRLA (valve regulated lead-acid) | |||||
Battery quantity and size | 6 x 9Ah | |||||
Charging current | 6A | |||||
Dimensions (W x D x H) | 17.2 x 3.4 x 24.8 in |
|||||
Weight | 49.6 lbs | |||||
Operating temperature | 32°F to 104° F (0°C to 40°C) | |||||
Altitude | 1000 m without derating | |||||
Warranty | 2 Year Warranty |
|||||
Manufacturing |
ISO 9001:2015, ISO 14001:2015, OHSAS 18001 | |||||
Performance |
IEC/EN 62040-3 | |||||
Optional communication cards | SNMP; ModBus; AS400; Environmental monitoring sensor probe |