The Vertiv™ Liebert® GXT5 UPS, with a capacity of 2000VA/1800W, is a 2U compact and efficient UPS solution for ensuring the health and availability of IT infrastructure. With online, double conversion technology, the Vertiv Liebert GXT5 UPS protects critical equipment against outages and every type of power disturbance without drawing on battery power, extending battery life and minimizing replacements.

Key Benefits of the Vertiv™ Liebert® GXT5 UPS:
  • Enhanced local and remote management capabilities enable users to understand the condition of the critical infrastructure space and take action when necessary
  • High power factor operation up to unity provides the highest available power (watt) for use by connected IT equipment, allowing for more connected devices 
  • Integrated serial connection for advanced console server integration or direct terminal control of the UPS 
  • Energy Star® 2.0 certification with efficiency in online (95%) and Active ECO (98%) modes
  • SNMP network communications with optional Liebert® RDU101 NIC and free Trellis™ Power Insight 
  • Gravity-sensing, color LCD for easy configuration and system diagnosis
  • Scalable power with auto-detection of external battery cabinets  
  • Connected Equipment Protection Plan

Liebert GXT5-2000LVRT2UXL UPS Specifications

Mechanical  
Height 3.4" (85 mm.)
Width 16.9" (430 mm.)
Depth 18.5" (470 mm.)
Weight 47.5 lb (21 kg)
Rack Height 2U
Color Black
Input AC  
Range Typical 120V
Range: 60-150V
Frequency 40-70Hz; Auto Sensing
Input Power Cord NEMA L5-20P or 5-20P plug (5-20P adapter included)
Output AC  
Output Receptacles L5-20R + 5-20R (x6)
Voltage Typical 120V
110/115/120VAC (user-configurable); ±3%
Waveform Sine wave
Utility (AC) Mode Overload >200% for 250ms;
150- 200% for 2 seconds
125- 150% for 50 seconds;
105-125% for 60 seconds
Battery  
Type Valve-regulated, non-spillable, lead acid
Backup Time 4 Minutes (100% Load)
12.3 Minutes(50% Load)
+1 External Battery Cabinet 22 Minutes (100% Load)
53.6 Minutes(50% Load)
Environmental  
Operating Temperature 32 to 104°F (0 to 40°C)
Storage Temperature -4 to 140°F (-20 to 60°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation 10,000 ft. (3,000m)
Storage Elevation 50,000 ft. (15,000m)
Audible Noise < 46dBA max @ 3 ft. (1m) front and sides
< 43dBA, at 3 ft. (1m) rear
Agency  
Surge Immunity ANSI C62.41 Category B
Transportation ISTA Procedure 1A
Safety UL 1778 4th Edition and CSA 22.2 No. 107.1
Emissions FCC Part 15 (Class A) - CISPR22 Class A (RFI)
Warranty 3 year warranty (Opt. 2 year)