General |
Topology |
Double-conversion |
Catalog Number |
K41512000000000 |
Part Number |
K41512000000000 |
Color |
Black |
Rating (VA/Watts) |
15000/13500 |
Diagnostics |
Full system self-test at startup |
UPS Bypass |
Automatic on overload or UPS failure |
Dimensions (H x W x D, inches) |
47.8 x 12 x 33.7 |
Weight (lbs) |
590 |
Warranty |
Two-year factory warranty |
Contents (Ships with the following items) |
1 ready-to-go UPS Software Suite CD User Guide |
Efficiency |
92% with nominal linear load; 91% with nominal computer load. |
|
|
Electrical Input |
Connection |
Hardwired - see manual for terminal block layout
|
Frequency |
50/60 Hz (45 to 65 Hz) |
Frequency Range |
45 to 65 Hz |
Input Power Factor |
P.F >0.99 typical, >0.96 frequency converter |
Generator Compatability |
Yes |
|
|
Electrical Output |
|
100/200, 110/220, 120/240 Vac 180° phase displacement; 120/208, 127/220 Vac 120° phase displacement |
Output Receptacles |
(1) PDM
|
On Utility Voltage Regulation |
Output voltage regulation ±1% Static; ±5% dynamic at 100% resistive load change |
On Battery Voltage Regulation |
Output voltage regulation ±1% Static; ±5% dynamic at 100% resistive load change |
Overload Capacity |
150% for 5 sec / 125% for 1 min (online), 110% for 10 min |
Voltage Wave Shape (On Battery) |
Sine Wave |
Transfer Time |
0 ms |
|
|
Battery |
Battery Management |
ABM technology |
Battery Type |
9Ah, sealed, lead-acid, maintenance-free |
Battery Replacement |
Field-replaceable |
Start On Battery |
Allows start of UPS without utility input |
Recharge Time |
Internal battery: approximately 3 hours to 80% usable capacity at nominal line voltage after full load discharge External battery: no more than 10x discharge time to 90% usable capacity at nominal line voltage after full load discharge |
|
|
Communications |
User Interface |
LCD Display with blue backlight |
LEDs |
(4) LEDs for notice and alarm |
Audible Alarms |
Yes |
Communication Ports |
(1) RS-232, (1) relay contact, (1) REPO, (2) environmental input |
Communication Slot |
(2) X-Slot communication bays |
Power Management Software |
Bundled Software Suite CD |
|
|
Environmental & Standards |
Audible Noise |
<53dBA at 1 meter (noise less room) typical |
Operating Temperature |
10°C to +40°C, +45°C with 7.5% derating; Batteries recommended max. +25�C |
Markings |
UL, cUL, CSA, CE and NOM-NYCE |
Storage Temperature |
-15°C to +25°C |
Relative Humidity |
0-95%, non condensing |