Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load
$4,699.99
Preowned Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load. Professionally tested & load banked with new Flame Retardant batteries installed.
Technical Specifications for 20 and 30 kVA1 | |
Power | |
Ratings (kVA/Watts) | 20 kVA/18 kW and 30 kVA/27 kW at 0.9 power factor |
Topology | Double conversion |
Electrical Input | |
Nominal input voltage | 208V/120V, 220V/127V +10, -15% 480V/277V, 600V (480+600 with transformer) 400V models also available |
Operating frequency | 50/60 Hz (45 to 65 Hz) |
Input power factor | 0.99 typical |
Input current distortion | <5% THD |
Electrical Output | |
Nominal output voltage | 208/120, 220/120 Vac |
Output voltage regulation | ±1% static; ±4% dynamic with 100% step load recovery within 1 ms response time |
Efficiency | 91%, typical |
Heat dissipation (BTU/hr) | 20 kVA models 6,762 @ 208V and 220V input 10,450 @ 480V and 600V (with input isolation transformer) 30 kVA models: 9,220 @ 208V and 220V input 13,831 @ 480V and 600V (with input isolation transformer) |
Battery | |
Battery type | 9 Ah, sealed, lead-acid, maintenance-free |
Battery replacement | Field-replaceable |
Charger | Default is 8A |
General | |
Diagnostics | Full system self-test at startup |
UPS bypass | Automatic on overload or UPS failure |
Parallel for redundancy | Yes, using Powerware Hot Sync technology and capacity |
Overload | 150% for 5 sec / 125% for 1 min (online), 110% for 10 min |
Communications | |
LCD display | Graphical LCD with blue backlight |
LEDs | (4) LEDs for notice and alarm |
Audible alarms | Yes |
Communication ports | (1) RS-232, (1) relay contact, (1) REPO, (2) environmental input |
Communication slot | (2) X-Slot communication bays |
Power management software | Bundled Software Suite CD |
Environmental | |
Operating temperature | 50–104ºF (10–40ºC), 45ºC with 7.5% derating; Optimal battery performance: 77ºF (25ºC) |
Storage temperature | 32–77ºF (0–25ºC); Recommended battery storage: 59–77ºF (15–25ºC) |
Relative humidity | 5–95%, non-condensing |
Audible noise | <58 dBA at 1 meter depending on load |
Altitude | <3000m |
Certifications | |
Safety certifications | UL1778 5th Edition, CSA C22.2 No. 107.3-14 |
EMC compliance | 47 CFR Part 15/ICES-003 Class A |
Quality | ISO 9001:2015, ISO 14001:2004 |
Surge | ANSI C62.41 Category B3, IEC 61000-4-5 |
Markings | cULus |
1. Due to continuous product improvements, program specifications are subject to change without notice.
Battery Run Times (in minutes)
VA | Watt | UPS + Internal 1 Battery |
Internal Battery + EBC - 36 |
Internal Battery + (1) EBC - 72 |
Internal Battery + (2) EBC - 72 |
30000 | 27000 | 11 | 31 | 56 | 89 |
29000 | 26100 | 11 | 33 | 58 | 90 |
28000 | 25200 | 12 | 35 | 60 | 93 |
27000 | 24300 | 12 | 38 | 62 | 95 |
26000 | 23400 | 13 | 40 | 65 | 98 |
25000 | 22500 | 14 | 43 | 68 | 101 |
24000 | 21600 | 14 | 46 | 71 | 103 |
23000 | 20700 | 15 | 48 | 74 | 106 |
22000 | 19800 | 16 | 51 | 76 | 109 |
21000 | 18900 | 17 | 53 | 79 | 111 |
20000 | 18000 | 18 | 56 | 82 | 114 |
19000 | 17100 | 19 | 58 | 85 | 117 |
18000 | 16200 | 20 | 62 | 88 | 120 |
17000 | 15300 | 22 | 66 | 92 | 130 |
16000 | 14400 | 24 | 71 | 96 | 142 |
15000 | 13500 | 26 | 75 | 101 | 154 |
14000 | 12600 | 28 | 79 | 105 | 166 |
13000 | 11700 | 31 | 84 | 110 | 178 |
12000 | 10800 | 35 | 88 | 114 | 201 |
11000 | 9900 | 38 | 94 | 119 | 256 |
10000 | 9000 | 42 | 101 | 134 | 251 |
7500 | 6750 | 58 | 117 | 188 | 347 |
5000 | 4500 | 90 | 188 | 294 | 543 |