Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load
Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load
Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load
Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load
Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load
Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load
Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load
Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load

Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load

$4,699.99 Sale Save

Only 0 left in stock

Preowned Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load.  Professionally tested & load banked with new Flame Retardant batteries installed.

Technical Specifications for 20 and 30 kVA1

Power
Ratings (kVA/Watts) 20 kVA/18 kW and 30 kVA/27 kW at 0.9 power factor
Topology Double conversion
Electrical Input
Nominal input voltage  208V/120V, 220V/127V +10, -15% 480V/277V, 600V (480+600 with transformer) 400V models also available
Operating frequency  50/60 Hz (45 to 65 Hz)
Input power factor  0.99 typical
Input current distortion  <5% THD
Electrical Output
Nominal output voltage   208/120, 220/120 Vac
Output voltage regulation ±1% static; ±4% dynamic with 100% step load recovery within 1 ms response time
Efficiency 91%, typical
Heat dissipation (BTU/hr) 20 kVA models
6,762 @ 208V and 220V input
10,450 @ 480V and 600V (with input isolation transformer)
30 kVA models:
9,220 @ 208V and 220V input
13,831 @ 480V and 600V (with input isolation transformer)
Battery
Battery type 9 Ah, sealed, lead-acid, maintenance-free

Battery replacement Field-replaceable
Charger Default is 8A
General
Diagnostics Full system self-test at startup
UPS bypass Automatic on overload or UPS failure
Parallel for redundancy Yes, using Powerware Hot Sync technology and capacity

Overload 150% for 5 sec / 125% for 1 min (online),
110% for 10 min
Communications
LCD display Graphical LCD with blue backlight
LEDs  (4) LEDs for notice and alarm
Audible alarms Yes
Communication ports (1) RS-232, (1) relay contact, (1) REPO, (2) environmental input
Communication slot (2) X-Slot communication bays
Power management software Bundled Software Suite CD
Environmental
Operating temperature 50–104ºF (10–40ºC), 45ºC with 7.5% derating; Optimal battery performance: 77ºF (25ºC)
Storage temperature 32–77ºF (0–25ºC); Recommended battery storage: 59–77ºF (15–25ºC)
Relative humidity 5–95%, non-condensing
Audible noise <58 dBA at 1 meter depending on load
Altitude <3000m
Certifications
Safety certifications UL1778 5th Edition, CSA C22.2 No. 107.3-14
EMC compliance 47 CFR Part 15/ICES-003 Class A
Quality ISO 9001:2015, ISO 14001:2004
Surge ANSI C62.41 Category B3, IEC 61000-4-5
Markings cULus

1. Due to continuous product improvements, program specifications are subject to change without notice.

Battery Run Times (in minutes)

 VA  Watt  UPS
 + Internal
1 Battery
 Internal
Battery +
EBC - 36
 Internal
Battery +
(1) EBC - 72
  Internal
Battery +
(2) EBC - 72
 30000 27000 11 31 56 89
29000 26100 11 33 58 90
28000 25200 12 35 60 93
27000 24300 12 38 62 95
26000 23400 13 40 65 98
25000 22500 14 43 68 101
24000 21600 14 46 71 103
23000 20700 15 48 74 106
22000 19800 16 51 76 109
21000 18900 17 53 79 111
20000 18000 18 56 82 114
19000 17100 19 58 85 117
18000 16200 20 62 88 120
17000 15300 22 66 92 130
16000 14400 24 71 96 142
15000 13500 26 75 101 154
14000 12600 28 79 105 166
13000 11700 31 84 110 178
12000 10800 35 88 114 201
11000 9900 38 94 119 256
10000 9000 42 101 134 251
7500 6750 58 117 188 347