Refurbished Mitsubishi DiamondPlus 1100 Series 50kVA 45KW 208VAC 3Ph UPS System
$17,999.99
Refurbished Mitsubishi DiamondPlus 1100 Series 50kVA 45KW 208VAC 3Ph UPS System
Professionally Refurbished System. Fully Tested and Load Banked. Includes Brand New Batteries.
Extended Service Plans Available - Please contact for additional details.
AC INPUT CHARACTERISTICS
Configuration: 3-phase, 4-wire, plus ground
Voltage: 208 V +15% ~ -30%
Frequency: 60 Hz +/- 10%
Reflected Current THD: 4% typical at 100% load; 7% typical at 50% load
AC OUTPUT
Configuration 3-phase, 4-wire
Voltage 120/208 V
Voltage Stability +/-1%
Frequency 60 Hz
Frequency Stability +/-0.01% in free running mode
Power Factor 0.9 nominal
Power Factor range 0.9 ~ 1.0 lagging (within output kW rating)
Voltage THD 2% typical THD at 100% linear load 5% typical THD at 100% non-linear load
Transient Response +/-3% typical at 100% load step +/-1% typical at loss/return of AC power +/-5% typical at load transfer to/from static bypass
Transient Recovery 16.7 ms
Voltage Unbalance 2% typical at 100% unbalanced load
Phase Displacement 1deg. typical at 100% load
Inverter Overload 125% for 60 seconds, 150% for 30 seconds
System Overload 1000% for 1 cycle (with bypass available)
Crest Factor Capabilities 2.5 : 1 E