Eaton 9PX 9PX3000GRT 3000VA/3000W 208V Online Double Conversion Rack / Tower UPS
$3,368.90
Eaton 9PX 9PX3000GRT 3000VA/3000W 208V Online Double Conversion Rack / Tower UPS
Eaton 9PX 9PX3000GRT Specifications:
General | |
Topology | Double-conversion online |
Configuration | Rack/Tower |
Catalog Number | 9PX3000GRT |
Color | Black and silver |
Rating (VA/Watts) | 3000/3000 |
Diagnostics | Full system self test at power up, and ABM test every 30 days |
UPS Bypass | EHBPL3000R-PDU1U optional |
Dimensions (H x W x D, inches) | 3.4 (2U) x 17.3 x 23.8 |
Dimensions (H x W x D, mm) | 86.5 x 440 x 605 |
Weight (kg) | 27.4 |
Weight (lbs) | 60.4 |
Warranty | 2 years |
Rail Kit Included | 4-post rail kit and tower pedestals included |
Remote Emergency Power off (REPO) | ROO/RPO: Rear deck emergency stop connectors (for remote on/off and power off) |
Contents (Ships with the following items) |
9PX3000GRT 3 kVA UPS 4-post rail kit Safety manual User manual Output cables (for G models) Input cables (for G models) Cable lockers (for G models) Tower pedestals RS-232 serial cable USB cable Intelligent Power Software Suite CD Communication card (optional) |
Efficiency | 93% with resistive load |
Electrical Input | |
Connection |
(1) NEMA L6-20P
|
Input Cord | Detachable L6-20P to C19 input cord; 6 feet (1.8 meters) |
Input Voltage Range | Full load: 176-276V, <40% load: 100-276V |
Nominal Voltage | 208V default (200/208/220/230/240V) |
Frequency | 50/60 Hz |
Frequency Range | 60 Hz: 50–70 Hz, 50 Hz: 40–60 Hz |
Input Power Factor | >.99 |
Input Current Distortion | <5% |
Electrical Output | |
Nominal Voltage | 208V default (200/208/220/230/240V) |
Output voltage regulation | ±1% steady-state |
Voltage THD | <3% for linear loads |
Output Receptacles |
(8) IEC-320-C13
(2) IEC-320-C19
|
Power Cables | (2) C14 to C13 jumpers |
Transfer Time | 0 ms |
Optional Extended Battery Module | 9PXEBM72RT |
Battery Description | Sealed, lead-acid; maintenance free |
Maximum number of extended battery modules (EBM) | Add up to 4 extended battery modules (EBM) |
Battery Management | ABM technology; 3-stage charging extends battery service life by 50% and provides advance warning for battery replacement |
Battery Replacement | Replaceable internal batteries and extended battery modules (EBMs) |
Start On Battery | Cold-start enabled; first cold start is always forbidden |
Communications | |
User Interface | Graphical display. UPS status in a single view. |
LEDs | 4 status-indicating LEDs |
Communication Ports | RS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables included |
Power Management Software | Eaton Intelligent Power Manager |
Environmental & Standards | |
RoHS Compliance | Yes |
Surge Protection | IEEE ANSI C62.41 Cat B2 |
Heat Dissipation (BTU) | Online: 619 Battery: 1150 (BTU/hr; battery full charged, resistive load) |
Audible Noise | <47 dB at 1 meter |
Operating Temperature | 0 to 40°C (32°F to 104°F) |
Safety markings | CE / cULus / NOM |
EMC Markings | IEC 62040-2 Class B Cat C2 / CISPR22 Class B / FCC part 15 Class B / VCCI Class B |
Storage Temperature | 0 to 35°C (32°F to 95°F); without batteries: -15 to 55°C (5°F to 131°F) |
Relative Humidity | 0 to 96% non-condensing |
Altitude | 0-1500m @ 0°C - 40 °C; 1500m-3000m @ 0°C - 35 °C |