Eaton 9PX 9PX6KSP 5.5kVA/4.9kW 120/208V Split Phase Online Rack/Tower UPS
Eaton 9PX 9PX6KSP 5.5kVA/4.9kW 120/208V Split Phase Online Rack/Tower UPS
Eaton 9PX 9PX6KSP 5.5kVA/4.9kW 120/208V Split Phase Online Rack/Tower UPS
Eaton 9PX 9PX6KSP 5.5kVA/4.9kW 120/208V Split Phase Online Rack/Tower UPS
Eaton 9PX 9PX6KSP 5.5kVA/4.9kW 120/208V Split Phase Online Rack/Tower UPS
Eaton 9PX 9PX6KSP 5.5kVA/4.9kW 120/208V Split Phase Online Rack/Tower UPS

Eaton 9PX 9PX6KSP 5.5kVA/4.9kW 120/208V Split Phase Online Rack/Tower UPS

$5,569.90 Sale Save

Only 0 left in stock

Eaton 9PX 9PX6KSP 5.5kVA/4.9kW 120/208V Split Phase Online Rack/Tower UPS

Eaton 9PX 9PX6KSP Specifications:
General
Topology Double-conversion online
Configuration Rack/Tower
Catalog Number 9PX6KSP
Color Black and silver
Rating (VA/Watts) 5500/4900
 
Diagnostics Full system self test at power up
Dimensions (H x W x D, inches) 6.8 (4U) x 17.3 x 25.6
Weight (lbs) 157.3
Warranty 2 years
Rail Kit Included 4-post rail kit and tower pedastals included
Remote Emergency Power off (REPO) ROO/RPO: Rear deck emergency stop connectors (for remote on/off and power off)
Electrical Input
Connection
(1) Terminal block with L14-30P***

Input Cord 6 feet (1.8 meters)
Input Voltage Range Full load: 176-276V; Derating: 100-276V
Nominal Voltage 120/208 default (120/240, 100/200, 110/220, 115/230, 127/220)
Frequency 50/60 Hz
Frequency Range 60 Hz: 50–70 Hz, 50 Hz: 40–60 Hz
Input Power Factor >99
Input Current Distortion <5%
 
Electrical Output
Nominal Voltage 120/208 default (120/240, 100/200, 110/220, 115/230, 127/220)
Output voltage regulation ±1% steady-state
Voltage THD <2% for linear loads
Output Receptacles
(6) NEMA 5-20R

(1) NEMA L6-30R

(1) NEMA L14-30R

Hardwired - see manual for terminal block layout

Power Factor 0.9
Transfer Time 0 ms
Circuit Breaker (4) 20A for 5-20R

​

Optional Extended Battery Module 9PXEBM240SP
Battery Description Sealed, lead-acid; maintenance free
Maximum number of extended battery modules (EBM) Add up to 4 extended battery modules (EBM)
Battery Management ABM technology; 3-stage charging extends battery service life by 50% and provides advance warning for battery replacement
Battery Replacement Hot-swappable internal batteries and extended battery modules (EBMs)
Start On Battery Cold-start enabled
 
Communications
User Interface Graphical display. UPS status in a single view.
LEDs 4 status-indicating LEDs
Communication Ports RS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables included
Communications Card Slots Gigabit Network Card (Network-M2) included
Power Management Software Eaton Intelligent Power Software Suite CD (included)
 
Environmental & Standards
RoHS Compliance Yes
Surge Protection IEEE ANSI C62.41 Cat B2
Audible Noise <55 dB at 1 meter
Operating Temperature 0 to 40°C (32°F to 104°F)
Safety markings CE / cULus / NOM
EMC Markings IEC 62040-2:2006 Cat C2 / CISPR22 Class A / FCC part 15 Class A
Storage Temperature 0 to 35°C (32°F to 95°F); without batteries: -15 to 60°C (5°F to 140°F)
Relative Humidity 0 to 95%
Altitude <3,000m for nominal power; -5°C temp derating every 500m