Power | |
Ratings (kVA/Watts) | 10 kVA/9 kW and 15 kVA/13.5 kW at 0.9 power factor |
Topology | Double conversion |
Electrical Input | |
Nominal input voltage | 208V/120V or 220V/127V three-phase 400V models also available |
Input voltage range | -15%, +10% from nominal at 100% load without depleting battery |
Operating frequency | 50/60 Hz (45 to 65 Hz) |
Input power factor | >0.99 typical, >0.96 frequency converter |
Input current distortion | 5% THD |
Electrical Output | |
Nominal output voltage | 208/120, 220/127 Vac |
Output voltage regulation | ±1% static; ±5% dynamic at 100% resistive load change, <1 ms response time |
Efficiency | 91%, typical |
Heat dissipation (BTU/hr) | 10 kVA models: 3,798 @ 208V and 220V input 6,294 @ 480V and 600V (with input isolation transformer) 15 kVA models: 5,122 @ 208V and 220V input 8,134 @ 480V and 600V (with input isolation transformer) |
Battery | |
Battery type | 9 Ah, sealed, lead-acid, maintenance-free |
Battery runtime | See battery backup time chart |
Battery management | ABM technology |
Battery replacement | Field-replaceable |
Charger | Default is 3.4A per battery string. Charger current is configurable from 0.5A to 25A per string with an overall maximum of 34A (limited by input current) |
Start-on-battery | Allows start of UPS without utility input |
General | |
Diagnostics | Full system self-test at startup |
UPS bypass | Automatic on overload or UPS failure |
Parallel for redundancy | Yes, using Powerware Hot Sync technology and capacity |
Dimensions and weights | See model selection table |
Overload (normal operation) | 150% for 5 sec / 125% for 1 min (online), 110% for 10 min |
Communications | |
LCD display | Graphical LCD with blue backlight |
LEDs | (4) LEDs for notice and alarm |
Audible alarms | Yes |
Communication ports | (1) RS-232, (1) relay contact, (1) REPO, (2) environmental input |
Communication slots | (2) X-Slot communication bays |
Power management software | Bundled Software Suite CD |
Environmental | |
Operating temperature | 50–104ºF (10–40ºC), 45ºC with 7.5% derating; Optimal battery performance: 77ºF (25ºC) |
Storage temperature | 32–77ºF (0–25ºC); Recommended battery storage: 59–77ºF (15–25ºC) |
Relative humidity | 0–95%, non-condensing |
Audible noise | <56 dBA at 1 meter (noiseless room) typical |
Altitude | 9,843 ft. (3000m) without derating |
Certifications | |
Safety certifications | UL1778 5th Edition, CSA C22.2 No. 107.3-14 |
EMC compliance | 47 CFR Part 15/ICES-003 Class A |
Quality | ISO 9001:2015, ISO 14001:2004 |
Surge | ANSI C62.41 Category B3, IEC 61000-4-5 |
Markings | cULus |
1. Due to continuous product improvements, program specifications are subject to change without notice.
Model Selection Table
Power Rating (kVA/kW)1 |
Description | Input/Output Voltage |
Part Number2 | Base Runtime | Dimensions (HxWxD, in.) |
Weight (lb.)3 |
10 / 9 | 2-high w/32 battery | 208/208 | KA1011100000010 | 8 | 32.2 x 12.0 x 33.5 | 373.0 |
10 / 9 | 3-high w/64 battery | 208/208 | KA1012100000010 | 22 | 47.8 x 12.0 x 33.5 | 609.0 |
10 / 9 | 2-high w/32 battery | 220/2204 | KA1011200000010 | 8 | 32.2 x 12.0 x 33.5 | 373.0 |
10 / 9 | 3-high w/64 battery | 220/2204 | KA1012200000010 | 22 | 47.8 x 12.0 x 33.5 | 609.0 |
10 / 9 | 3-high w/32 battery and input isolation transformer | 480/208 | KA1013400000010 | 8 | 47.8 x 12.0 x 33.5 | 577.0 |
10 / 9 | 3-high w/32 battery and input isolation transformer | 600/208 | KA1013600000010 | 8 | 47.8 x 12.0 x 33.5 | 577.0 |
15 / 13.5 | 2-high w/32 battery | 208/208 | KA1511100000010 | 4 | 32.2 x 12.0 x 33.5 | 373.0 |
15 / 13.5 | 3-high w/64 battery | 208/208 | KA1512100000010 | 13 | 47.8 x 12.0 x 33.5 | 609.0 |
15 / 13.5 | 2-high w/32 battery | 220/2204 | KA1511200000010 | 4 | 32.2 x 12.0 x 33.5 | 373.0 |
15 / 13.5 | 3-high w/64 battery | 220/2204 | KA1512200000010 | 13 | 47.8 x 12.0 x 33.5 | 609.0 |
15 / 13.5 | 3-high w/32 battery and input isolation transformer | 480/208 | KA1513400000010 | 4 | 47.8 x 12.0 x 33.5 | 577.0 |
15 / 13.5 | 3-high w/32 battery and input isolation transformer | 600/208 | KA1513600000010 | 4 | 47.8 x 12.0 x 33.5 | 577.0 |
Recent News
Lighting Inverters: Ensuring Uninterrupted Safety and Compliance for Emergency Systems
What is a Lighting Inverter? A lighting inverter converts DC battery power to standard AC voltages to provide backup for lighting systems during...
From Power Outages to Business Continuity: How UPS Systems Save the Day
Businesses can't afford unexpected power outages. Even a brief disruption can lead to lost productivity, corrupted data, and decreased customer satisfaction. That's where Uninterruptible...
Power Protection Trends for 2025
As changes in power protection continues to evolve, 2024 has brought significant shifts in the way businesses and organizations approach uninterruptible power supply (UPS) systems...