Eaton 9355 10kVA 9kW 220/220V 64-Battery 3-High 3-Phase Tower UPS
Eaton 9355 10kVA 9kW 220/220V 64-Battery 3-High 3-Phase Tower UPS
Eaton 9355 10kVA 9kW 220/220V 64-Battery 3-High 3-Phase Tower UPS
Eaton 9355 10kVA 9kW 220/220V 64-Battery 3-High 3-Phase Tower UPS

Eaton 9355 10kVA 9kW 220/220V 64-Battery 3-High 3-Phase Tower UPS

$14,827.99 Sale Save

Only 0 left in stock

Eaton 9355 10kVA 9kW 220/220V 64-Battery 3-High 3-Phase Tower UPS


The Eaton 9355 UPS provides premium double-conversion backup power and scalable battery runtimes for IT and electrical engineering infrastructure in corporate, healthcare, banking and industrial applications. Packing maximum battery runtime into a very small footprint, the 9355 UPS is a complete three-phase power protection solution. The 9355 can be equipped with an integrated, customizable power distribution module that includes a maintenance bypass switch.



Power
Ratings (kVA/Watts) 10 kVA/9 kW and 15 kVA/13.5 kW at 0.9 power factor
Topology Double conversion
Electrical Input
Nominal input voltage  208V/120V or 220V/127V three-phase 400V models also available
Input voltage range  -15%, +10% from nominal at 100% load without depleting battery
Operating frequency  50/60 Hz (45 to 65 Hz)
Input power factor  >0.99 typical, >0.96 frequency converter
Input current distortion  5% THD
Electrical Output
Nominal output voltage   208/120, 220/127 Vac
Output voltage regulation ±1% static; ±5% dynamic at 100% resistive load change, <1 ms response time
Efficiency 91%, typical
Heat dissipation (BTU/hr) 10 kVA models:
3,798 @ 208V and 220V input
6,294 @ 480V and 600V (with input isolation transformer)
15 kVA models:
5,122 @ 208V and 220V input
8,134 @ 480V and 600V (with input isolation transformer)
Battery
Battery type 9 Ah, sealed, lead-acid, maintenance-free
Battery runtime See battery backup time chart
Battery management ABM technology
Battery replacement Field-replaceable
Charger Default is 3.4A per battery string. Charger current is configurable from 0.5A to 25A per string with an overall maximum of 34A (limited by input current)
Start-on-battery Allows start of UPS without utility input
General
Diagnostics Full system self-test at startup
UPS bypass Automatic on overload or UPS failure
Parallel for redundancy Yes, using Powerware Hot Sync technology and capacity
Dimensions and weights See model selection table
Overload (normal operation) 150% for 5 sec / 125% for 1 min (online),
110% for 10 min
Communications
LCD display Graphical LCD with blue backlight
LEDs  (4) LEDs for notice and alarm
Audible alarms Yes
Communication ports (1) RS-232, (1) relay contact, (1) REPO,
(2) environmental input
Communication slots (2) X-Slot communication bays
Power management software Bundled Software Suite CD
Environmental
Operating temperature 50–104ºF (10–40ºC), 45ºC with 7.5% derating; Optimal battery performance: 77ºF (25ºC)
Storage temperature 32–77ºF (0–25ºC); Recommended battery storage: 59–77ºF (15–25ºC)
Relative humidity 0–95%, non-condensing
Audible noise <56 dBA at 1 meter (noiseless room) typical
Altitude 9,843 ft. (3000m) without derating
Certifications
Safety certifications UL1778 5th Edition, CSA C22.2 No. 107.3-14
EMC compliance 47 CFR Part 15/ICES-003 Class A
Quality ISO 9001:2015, ISO 14001:2004
Surge ANSI C62.41 Category B3, IEC 61000-4-5
Markings cULus

1. Due to continuous product improvements, program specifications are subject to change without notice.

Model Selection Table

Power
Rating (kVA/kW)1
Description Input/Output
Voltage
Part Number2 Base Runtime Dimensions
(HxWxD, in.)
Weight
(lb.)3
10 / 9 2-high w/32 battery 208/208 KA1011100000010 8 32.2 x 12.0 x 33.5 373.0
10 / 9  3-high w/64 battery 208/208 KA1012100000010 22 47.8 x 12.0 x 33.5 609.0
10 / 9 2-high w/32 battery 220/2204 KA1011200000010 8 32.2 x 12.0 x 33.5 373.0
10 / 9 3-high w/64 battery 220/2204 KA1012200000010 22 47.8 x 12.0 x 33.5 609.0
10 / 9 3-high w/32 battery and input isolation transformer 480/208 KA1013400000010 8 47.8 x 12.0 x 33.5 577.0
10 / 9 3-high w/32 battery and input isolation transformer 600/208 KA1013600000010 8 47.8 x 12.0 x 33.5 577.0
15 / 13.5 2-high w/32 battery 208/208 KA1511100000010 4 32.2 x 12.0 x 33.5 373.0
15 / 13.5 3-high w/64 battery 208/208 KA1512100000010 13 47.8 x 12.0 x 33.5 609.0
15 / 13.5 2-high w/32 battery 220/2204 KA1511200000010 4 32.2 x 12.0 x 33.5 373.0
15 / 13.5 3-high w/64 battery 220/2204  KA1512200000010 13 47.8 x 12.0 x 33.5 609.0
15 / 13.5 3-high w/32 battery and input isolation transformer 480/208 KA1513400000010 4 47.8 x 12.0 x 33.5 577.0
15 / 13.5 3-high w/32 battery and input isolation transformer 600/208 KA1513600000010 4 47.8 x 12.0 x 33.5 577.0