Eaton 9355 30kVA 27kW 208/208V 3-Phase UPS w/New Batteries 11-Min Full Load
Technical Specifications for 20 and 30 kVA1 | |
Power | |
Ratings (kVA/Watts) | 20 kVA/18 kW and 30 kVA/27 kW at 0.9 power factor |
Topology | Double conversion |
Electrical Input | |
Nominal input voltage | 208V/120V, 220V/127V +10, -15% 480V/277V, 600V (480+600 with transformer) 400V models also available |
Operating frequency | 50/60 Hz (45 to 65 Hz) |
Input power factor | 0.99 typical |
Input current distortion | <5% THD |
Electrical Output | |
Nominal output voltage | 208/120, 220/120 Vac |
Output voltage regulation | ±1% static; ±4% dynamic with 100% step load recovery within 1 ms response time |
Efficiency | 91%, typical |
Heat dissipation (BTU/hr) | 20 kVA models 6,762 @ 208V and 220V input 10,450 @ 480V and 600V (with input isolation transformer) 30 kVA models: 9,220 @ 208V and 220V input 13,831 @ 480V and 600V (with input isolation transformer) |
Battery | |
Battery type | 9 Ah, sealed, lead-acid, maintenance-free |
Battery replacement | Field-replaceable |
Charger | Default is 8A |
General | |
Diagnostics | Full system self-test at startup |
UPS bypass | Automatic on overload or UPS failure |
Parallel for redundancy | Yes, using Powerware Hot Sync technology and capacity |
Overload | 150% for 5 sec / 125% for 1 min (online), 110% for 10 min |
Communications | |
LCD display | Graphical LCD with blue backlight |
LEDs | (4) LEDs for notice and alarm |
Audible alarms | Yes |
Communication ports | (1) RS-232, (1) relay contact, (1) REPO, (2) environmental input |
Communication slot | (2) X-Slot communication bays |
Power management software | Bundled Software Suite CD |
Environmental | |
Operating temperature | 50–104ºF (10–40ºC), 45ºC with 7.5% derating; Optimal battery performance: 77ºF (25ºC) |
Storage temperature | 32–77ºF (0–25ºC); Recommended battery storage: 59–77ºF (15–25ºC) |
Relative humidity | 5–95%, non-condensing |
Audible noise | <58 dBA at 1 meter depending on load |
Altitude | <3000m |
Certifications | |
Safety certifications | UL1778 5th Edition, CSA C22.2 No. 107.3-14 |
EMC compliance | 47 CFR Part 15/ICES-003 Class A |
Quality | ISO 9001:2015, ISO 14001:2004 |
Surge | ANSI C62.41 Category B3, IEC 61000-4-5 |
Markings | cULus |
1. Due to continuous product improvements, program specifications are subject to change without notice.
Battery Run Times (in minutes)
VA | Watt | UPS + Internal 1 Battery |
Internal Battery + EBC - 36 |
Internal Battery + (1) EBC - 72 |
Internal Battery + (2) EBC - 72 |
30000 | 27000 | 11 | 31 | 56 | 89 |
29000 | 26100 | 11 | 33 | 58 | 90 |
28000 | 25200 | 12 | 35 | 60 | 93 |
27000 | 24300 | 12 | 38 | 62 | 95 |
26000 | 23400 | 13 | 40 | 65 | 98 |
25000 | 22500 | 14 | 43 | 68 | 101 |
24000 | 21600 | 14 | 46 | 71 | 103 |
23000 | 20700 | 15 | 48 | 74 | 106 |
22000 | 19800 | 16 | 51 | 76 | 109 |
21000 | 18900 | 17 | 53 | 79 | 111 |
20000 | 18000 | 18 | 56 | 82 | 114 |
19000 | 17100 | 19 | 58 | 85 | 117 |
18000 | 16200 | 20 | 62 | 88 | 120 |
17000 | 15300 | 22 | 66 | 92 | 130 |
16000 | 14400 | 24 | 71 | 96 | 142 |
15000 | 13500 | 26 | 75 | 101 | 154 |
14000 | 12600 | 28 | 79 | 105 | 166 |
13000 | 11700 | 31 | 84 | 110 | 178 |
12000 | 10800 | 35 | 88 | 114 | 201 |
11000 | 9900 | 38 | 94 | 119 | 256 |
10000 | 9000 | 42 | 101 | 134 | 251 |
7500 | 6750 | 58 | 117 | 188 | 347 |
5000 | 4500 | 90 | 188 | 294 | 543 |
Recent News
How Education Systems Rely on UPS Systems
As students return to classrooms this fall, schools, colleges, and universities face increasing demands on their technology and power infrastructure. From digital learning platforms to...
Why Modular UPS Systems Are a Smart Power Strategy
Today’s IT environments are evolving fast. From growing server rooms to decentralized facilities, one thing remains constant—reliable, scalable power protection is essential. Traditional UPS...
How to Choose the Right UPS System for Your Business: A No-Nonsense Buyer’s Guide
Downtime is expensive. Whether you're running a data center, a healthcare facility, or a manufacturing line, power interruptions can disrupt operations and lead to major...