APC Symmetra PX SYPM25KD 25kVA/25kW 480V Power Module (Preowned)

$2,329.90
Adding to Cart Added to Cart

* Preowned APC Symmetra PX SYPM25KD 25kVA / 25kW 480V Power Module 

Recently removed from operational system. Fully tested for functionality. 

 

Technical Specifications:

 

Output

  • Max Configurable Power (Watts): 25.0kWatts / 25.0kVA
  • Efficiency at Full Load: 96.0 %
  • Output Voltage Distortion: Less than 2%
  • Output Frequency (not synced): 60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for
  • 50Hz nominal
  • Load Crest Factor: Unlimited
  • Topology: Double Conversion Online
  • Waveform type: Sine wave
  • Overload Operation: 10 minutes @ 125% and 60 seconds @ 150%
  • Output Voltage THD: < 2% for 0 to 100% linear load and < 6% for full non linear load
  • Output Voltage Tolerance: +/-1% static and +/- 5% at 100% load step

 

Input

  • Input frequency: 40 - 70 Hz
  • Input voltage range for main operations: 340 - 460 (400V), 408 - 552 (480)V
  • Efficiency at Full Load: 96.0 %
  • Input Total Harmonic Distortion: Less than 5% for full load
  • Input Power Factor at Full Load: 0.99

 

Physical

  • Maximum Height: 6.81inches (173MM, 17.3CM)
  • Maximum Width: 17.8inches (452MM, 45.2CM)
  • Maximum Depth: 27.76inches (705MM, 70.5CM)
  • Net Weight: 92.4lbs. (42.0KG)
  • Shipping weight: 106.0lbs. (48.18KG)
  • Shipping Height: 11.22inches (285MM, 28.5CM)
  • Shipping Width: 23.03inches (585MM, 58.5CM)
  • Shipping Depth: 36.81inches (935MM, 93.5CM)
  • Color: Black
  • Units per Pallet: 6.0

Environmental

  • Operating Temperature: 32 - 104 °F (0 - 40 °C)
  • Operating Relative Humidity: 0 - 95 %
  • Operating Elevation: 0-3333ft (0-999.9meters)
  • Storage Temperature: -15 - 40 °C
  • Storage Relative Humidity: 0 - 95 %
  • Storage Elevation: 0-50000ft (0-15000meters)
  • Audible noise at 1 meter from surface of unit: 54.0dBA
  • Approvals: cUL Listed, CE, UL Listed, VDE
  • Sustainable Offer Status: RoHS Compliant

 

 

Recent News

Why Does Room Temperature Have Such a Big Impact on UPS Battery Life?

Why Does Room Temperature Have Such a Big Impact on UPS Battery Life?

When it comes to protecting critical equipment, most people focus on the UPS itself, its capacity, runtime, and features. However, one of the biggest factors...

Read more
Single-Phase vs. Three-Phase UPS: What Growing Businesses Get Wrong

Single-Phase vs. Three-Phase UPS: What Growing Businesses Get Wrong

As businesses grow, so do their power demands. What once worked for a small server room or office network can quickly become inadequate as more...

Read more
How Heat Affects Data Centers and Why Your UPS System Is at Risk

How Heat Affects Data Centers and Why Your UPS System Is at Risk

As temperatures rise and computing demands continue to grow, heat has become one of the most serious threats facing modern data centers, server rooms, and...

Read more