Eaton 9155 10kVA 9kW 32-Battery 3-High w/Transformer Module Tower UPS
| General | |
| Topology | Double-conversion |
| Catalog Number | K41013000000000 |
| Part Number | K41013000000000 |
| Color | Black |
| Rating (VA/Watts) | 10000/9000 |
| Diagnostics | Full system self-test at startup |
| UPS Bypass | Automatic on overload or UPS failure |
| Dimensions (H x W x D, inches) | 47.8 x 12 x 33.7 |
| Weight (lbs) | 558 |
| Warranty | Two-year factory warranty |
| Contents (Ships with the following items) |
1 ready-to-go UPS Software Suite CD User Guide |
| Efficiency | 92% with nominal linear load; 91% with nominal computer load. |
| Electrical Input | |
| Connection |
Hardwired - see manual for terminal block layout
|
| Frequency | 50/60 Hz (45 to 65 Hz) |
| Frequency Range | 45 to 65 Hz |
| Input Power Factor | P.F >0.99 typical, >0.96 frequency converter |
| Generator Compatability | Yes |
| Electrical Output | |
| 100/200, 110/220, 120/240 Vac 180° phase displacement; 120/208, 127/220 Vac 120° phase displacement | |
| Output Receptacles |
(1) PDM
|
| On Utility Voltage Regulation | Output voltage regulation ±1% Static; ±5% dynamic at 100% resistive load change |
| On Battery Voltage Regulation | Output voltage regulation ±1% Static; ±5% dynamic at 100% resistive load change |
| Overload Capacity | 150% for 5 sec / 125% for 1 min (online), 110% for 10 min |
| Voltage Wave Shape (On Battery) | Sine Wave |
| Transfer Time | 0 ms |
| Battery | |
| Battery Management | ABM technology |
| Battery Type | 9Ah, sealed, lead-acid, maintenance-free |
| Battery Replacement | Field-replaceable |
| Start On Battery | Allows start of UPS without utility input |
| Recharge Time | Internal battery: approximately 3 hours to 80% usable capacity at nominal line voltage after full load discharge External battery: no more than 10x discharge time to 90% usable capacity at nominal line voltage after full load discharge |
| Communications | |
| User Interface | LCD Display with blue backlight |
| LEDs | (4) LEDs for notice and alarm |
| Audible Alarms | Yes |
| Communication Ports | (1) RS-232, (1) relay contact, (1) REPO, (2) environmental input |
| Communication Slot | (2) X-Slot communication bays |
| Power Management Software | Bundled Software Suite CD |
| Environmental & Standards | |
| Audible Noise | <53dBA at 1 meter (noise less room) typical |
| Operating Temperature | 10°C to +40°C, +45°C with 7.5% derating; Batteries recommended max. +25�C |
| Markings | UL, cUL, CSA, CE and NOM-NYCE |
| Storage Temperature | -15°C to +25°C |
| Relative Humidity | 0-95%, non condensing |
Save 10% on Your First Order
Join our email list for exclusive pricing, product updates, and offers built for your business. We'll only send what's useful, never spam.
New subscribers get 10% off their first order—up to $250.
Recent News
Why Runtime Isn't the Only Thing That Matters When Buying a UPS
Learn why UPS runtime is only one factor when buying a battery backup. Discover how sizing, battery technology, reliability, and power quality affect your UPS...