Power |
Ratings (kVA/Watts) |
10 kVA/9 kW and 15 kVA/13.5 kW at 0.9 power factor |
Topology |
Double conversion |
Electrical Input |
Nominal input voltage |
208V/120V or 220V/127V three-phase 400V models also available |
Input voltage range |
-15%, +10% from nominal at 100% load without depleting battery |
Operating frequency |
50/60 Hz (45 to 65 Hz) |
Input power factor |
>0.99 typical, >0.96 frequency converter |
Input current distortion |
5% THD |
Electrical Output |
Nominal output voltage |
208/120, 220/127 Vac |
Output voltage regulation |
±1% static; ±5% dynamic at 100% resistive load change, <1 ms response time |
Efficiency |
91%, typical |
Heat dissipation (BTU/hr) |
10 kVA models: 3,798 @ 208V and 220V input 6,294 @ 480V and 600V (with input isolation transformer) 15 kVA models: 5,122 @ 208V and 220V input 8,134 @ 480V and 600V (with input isolation transformer) |
Battery |
Battery type |
9 Ah, sealed, lead-acid, maintenance-free |
Battery runtime |
See battery backup time chart |
Battery management |
ABM technology |
Battery replacement |
Field-replaceable |
Charger |
Default is 3.4A per battery string. Charger current is configurable from 0.5A to 25A per string with an overall maximum of 34A (limited by input current) |
Start-on-battery |
Allows start of UPS without utility input |
General |
Diagnostics |
Full system self-test at startup |
UPS bypass |
Automatic on overload or UPS failure |
Parallel for redundancy |
Yes, using Powerware Hot Sync technology and capacity |
Dimensions and weights |
See model selection table |
Overload (normal operation) |
150% for 5 sec / 125% for 1 min (online), 110% for 10 min |
Communications |
LCD display |
Graphical LCD with blue backlight |
LEDs |
(4) LEDs for notice and alarm |
Audible alarms |
Yes |
Communication ports |
(1) RS-232, (1) relay contact, (1) REPO, (2) environmental input |
Communication slots |
(2) X-Slot communication bays |
Power management software |
Bundled Software Suite CD |
Environmental |
Operating temperature |
50–104ºF (10–40ºC), 45ºC with 7.5% derating; Optimal battery performance: 77ºF (25ºC) |
Storage temperature |
32–77ºF (0–25ºC); Recommended battery storage: 59–77ºF (15–25ºC) |
Relative humidity |
0–95%, non-condensing |
Audible noise |
<56 dBA at 1 meter (noiseless room) typical |
Altitude |
9,843 ft. (3000m) without derating |
Certifications |
Safety certifications |
UL1778 5th Edition, CSA C22.2 No. 107.3-14 |
EMC compliance |
47 CFR Part 15/ICES-003 Class A |
Quality |
ISO 9001:2015, ISO 14001:2004 |
Surge |
ANSI C62.41 Category B3, IEC 61000-4-5 |
Markings |
cULus |