Toshiba 3000 SP 6kVA Modular Online UPS System – 3-Phase, True Double Conversion, Scalable Backup Power (30S0D6000HXH)
Power your critical infrastructure with confidence using the Toshiba 3000 SP Series 6kVA Modular 3-Phase UPS System. This next-generation online double-conversion UPS offers true VFI performance with a unity power factor (6kVA = 6kW) to ensure 100% usable power delivery. Designed with flexibility in mind, the system is fully modular and scalable, allowing expansion up to 24kVA in 6kVA increments within the same frame. The hot-swappable power and battery modules allow for seamless maintenance and system growth without downtime.
Built for demanding environments like IT networks, commercial edge locations, manufacturing floors, and SMB data centers, the 3000 SP delivers clean, regulated power with advanced remote management via the embedded RemotEye® 5 IIoT network card. A large 10” HMI LCD touchscreen ensures intuitive local control, while ECO Mode efficiency up to 98% minimizes energy consumption
Highlights:
- 6kVA / 6kW Unity Power Factor – 100% usable power without derating
- True Online Double Conversion – Isolates and protects against power anomalies
- Modular, Scalable Design – Expand up to 24kVA in the same system cabinet
- Hot-Swappable Power & Battery Modules – Simplifies service and uptime
- RemotEye® 5 Monitoring – Built-in IIoT remote interface with SNMP, Modbus, BACnet & HTTPS
- 10” HMI LCD Touchscreen – Local interface for full system control and diagnostics
- High-Efficiency ECO Mode – Up to 98% efficiency for energy savings
- N+X Redundancy Support – Reliable power continuity for mission-critical environments
- Compact Rack Footprint – Space-saving 30U system enclosure
- Advanced Safety & Configurability – Built-in backfeed protection, flexible battery setup
Specifications:
- Model: Toshiba 3000 SP – 6kVA
- Model Number: 30S0D6000HXH
- Topology: True Online Double Conversion (VFI)
- Power Rating: 6kVA / 6kW (Unity Power Factor)
- Input Configuration: 2-Phase + Neutral + Ground (240/120V or 208/120V)
- Input Voltage Range: +10% to -10%
- Input Frequency: 50/60Hz ±10% (Selectable)
- Input Power Factor: 0.99 at full load
- Max Input Current: 32A
- Output Configuration: 2-Phase + Neutral + Ground (240/120V or 208/120V)
- Voltage Regulation: ±1% (240V) / ±3% (208V)
- Output Frequency: 50/60Hz Auto Sensing
- Crest Factor: 3:1
- Voltage THD: < 4% (linear load), < 5% (non-linear load)
- Inverter Overload Capacity: Up to 150% (varies by duration)
- Battery Type: Internal VRLA (Valve Regulated Lead Acid)
- Battery Runtime: ~7 minutes @ 100% load (1:1 config)
- Battery Voltage: ±120VDC
- Charge Current (Adj.): 4A
- Monitoring & Interface: RS232, USB, Dry Contacts, EPO, RemotEye® 5 IIoT Network Card
- Display: 10" HMI LCD Touch Panel
- Efficiency (AC-AC): >89% (typical); ECO Mode up to 98%
- Cooling: Forced Air
- Operating Temp: 32°F to 104°F (0°C to 40°C)
- Humidity: 30–95% non-condensing
- Enclosure Rating: NEMA 1
- Noise Level: 72 dB @ 1 meter
- System Dimensions (W×D×H): 23.6" × 41.2" × 58.0" (598 × 1064 × 1472 mm)
- System Weight: 503 lbs (228 kg)
- Certifications: UL, cUL, FCC Class A, ISO 9001, ISO 14001, IEC/EN 62040-1
- Warranty: 3 year warranty
Recent News
Why Modular UPS Systems Are a Smart Power Strategy
Today’s IT environments are evolving fast. From growing server rooms to decentralized facilities, one thing remains constant—reliable, scalable power protection is essential. Traditional UPS...
How to Choose the Right UPS System for Your Business: A No-Nonsense Buyer’s Guide
Downtime is expensive. Whether you're running a data center, a healthcare facility, or a manufacturing line, power interruptions can disrupt operations and lead to major...
Hospital Emergency Backup Failures – Why Medical Facilities Can’t Afford a UPS Failure
In the high-stakes world of healthcare, seconds can save lives—or cost them. When power outages strike, hospitals and medical facilities rely heavily on uninterruptible power...