Eaton 5P 5P750 750VA/600W 120V Tower Line Interactive UPS
$434.90
Eaton 5P 5P750 750VA/600W 120V Tower Line Interactive UPS
General | |
Topology | Line interactive |
Configuration | Tower |
Color | Black and silver |
Rating (VA/Watts) | 750/600 |
Diagnostics | Full system self-test at power up |
Dimensions (H x W x D, inches) | 9.1 x 5.9 x 13.6 |
Dimensions (H x W x D, mm) | 230 x 150 x 345 |
Weight (kg) | 10.71 |
Weight (lbs) | 23.6 |
Warranty | 3 years on electronics, 3 years on batteries with registration |
Remote Emergency Power off (REPO) | ROO/RPO: Rear terminal block connector for remote on/off and power off |
Contents (Ships with the following items) |
5P UPS User manual CD Intelligent Power Software Suite CD Quick start guide USB cable RS-232 serial cable |
Efficiency | up to 97% |
Electrical Input | |
Connection |
(1) NEMA 5-15P
|
Input Cord | 6 feet (1.8 meters) |
Input Voltage Range | 89–151 Vac (adjustable to 70–153 Vac) |
Nominal Voltage | 120 Vac (adjustable to100/120/127 Vac) |
Frequency | 50/60 Hz (auto-sensing) |
Frequency Range | 47–70 Hz (50 Hz system), 56.5–70 Hz (60 Hz system), 40-70 Hz in low-sensitivity mode |
Electrical Output | |
Nominal Voltage | 120V default (100/120/125V) |
Output Receptacles |
(8) NEMA 5-15R
|
On Utility Voltage Regulation | 102–132 Vac |
On Battery Voltage Regulation | -10%, +6% of nominal |
Output Frequency | 50/60 Hz ±0.1 % (autosensing) |
Load Segments | Group 1: (2) 5-15R outlets; Group 2: (2) 5-15R outlets view load segments application note |
Communications | |
User Interface | LCD graphical display |
LEDs | Load protected, on battery and fault |
Communication Ports | RS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables included |
Communications Card Slots | One slot; Gigabit Network Card (Network-M2) is optional |
Power Management Software | Eaton Intelligent Power Software Suite CD (included) |
Environmental & Standards | |
RoHS Compliance | Yes |
Heat Dissipation (BTU) | Line: 82, Battery 389 |
Audible Noise | <45 dB at 1 meter |
Operating Temperature | 0 to 35°C (32°F to 95°F) |
Performance - Safety - EMC | UL 1778, UL497A |
Safety markings | cULus, CE |
EMC Markings | IEC 62040-2 C1-C2 / EN 55024 / CISPR22 Class B / FCC part 15 Class B |
Storage Temperature | -15°C – 40°C (5°F – 104°F) |
Relative Humidity | 0–90% non-condensing |
Altitude | Up to 10,000 ft (3000m) without de-rating |