Vertiv Liebert GXT5-3000LVRT2UXLN 3000VA 2700W 120V Rack/Tower Online UPS with Network Card
$3,579.90
GXT5-3000LVRT2UXLN; Liebert® GXT5 UPS, 3000VA/2700W, 120V with Network Card
The Vertiv™ Liebert® GXT5 UPS, with a capacity of 3000VA/2700W, is a 2U compact and efficient UPS solution for ensuring the health and availability of IT infrastructure. With online, double conversion technology, the Vertiv Liebert GXT5 UPS protects critical equipment against outages and every type of power disturbance without drawing on battery power, extending battery life and minimizing replacements.
KEY BENEFITS:
- Enhanced local and remote management capabilities enable users to understand the condition of the critical infrastructure space and take action when necessary
- High power factor operation up to unity provides the highest available power (watt) for use by connected IT equipment, allowing for more connected devices
- Integrated serial connection for advanced console server integration or direct terminal control of the UPS
- Energy Star® 2.0 certification with efficiency in online (95%) and Active ECO (98%) modes
- SNMP network communications with optional Liebert® RDU101 NIC and free Trellis™ Power Insight
- Gravity-sensing, color LCD for easy configuration and system diagnosis
- Scalable power with auto-detection of external battery cabinets
- Connected Equipment Protection Plan
- Supports SNMP, web, and environmental sensors with the RDU101 communications card
Liebert GXT5-3000LVRT2UXLN UPS Specifications
Mechanical | |
Height | 3.4" (85 mm.) |
Width | 16.9" (430 mm.) |
Depth | 21.3" (540 mm.) |
Weight | 66 lb (30 kg) |
Rack Height | 2U |
Color | Black |
Input AC | |
Range | Typical 120V Range: 60-150V |
Frequency | 40-70Hz; Auto Sensing |
Input Power Cord | 10 ft. attached w/ NEMA L5-30P plug |
Output AC | |
Output Receptacles | L5-30R+5-20R × 6 |
Voltage | Typical 120V 110/115/120VAC (user-configurable); ±3% |
Waveform | Sine wave |
Utility (AC) Mode Overload | >200% for 250ms; 150- 200% for 2 seconds; 125- 150% for 10 seconds; 105-125% for 15 seconds |
Battery | |
Type | Valve-regulated, non-spillable, lead acid |
Backup Time |
4 Minutes (100% Load) 12.6 Minutes(50% Load) |
+1 External Battery Cabinet | 22.2 Minutes (100% Load) 54.6 Minutes(50% Load) |
Environmental | |
Operating Temperature | 32 to 104°F (0 to 40°C) |
Storage Temperature | -4 to 140°F (-20 to 60°C) |
Relative Humidity | 0% to 95%, non-condensing |
Operating Elevation | 10,000 ft. (3,000m) |
Storage Elevation | 50,000 ft. (15,000m) |
Audible Noise | < 46dBA max @ 3 ft. (1m) front and sides < 43dBA, at 3 ft. (1m) rear |
Agency | |
Surge Immunity | ANSI C62.41 Category B |
Transportation | ISTA Procedure 1A |
Safety | UL 1778 4th Edition and CSA 22.2 No. 107.3 |
Emissions | FCC Part 15 (Class A) - CISPR22 Class A (RFI) |
Warranty | Standard 3 year warranty (Opt. 2 year) |